A warmer interior is less dense. Outside air enters below the neutral plane and leaves above it.
A warmer interior is less dense. Outside air enters below the neutral plane and leaves above it.
Imagine taking pressure readings at evenly spaced heights along the wall. The sign change brackets the neutral plane. Compare that measured crossing with the analytical solution.
Percent differences are calculated from the live model. “Static” means the model predicts no through-flow.
At a height z, the indoor-minus-outdoor pressure difference is modelled as
C is the unknown indoor pressure offset. The solver adjusts it until the signed mass flow through the two openings sums to zero. The neutral pressure plane is the height where Δp = 0.
Temperature is converted to kelvin. The density relation uses the ideal-gas approximation for dry air. Flow through each opening follows the orifice equation; the source-side density is used for inflow or outflow as appropriate.
The air is treated as dry, well mixed and at a uniform temperature indoors and outdoors. The building is represented by one vertical pressure line and two openings. Real buildings have leakage paths, multiple rooms, thermal storage, changing wind pressure, façade effects, turbulence, doors, ducts and mechanical systems. The model does not predict comfort, indoor air quality or code compliance. A real building needs measured geometry, pressure coefficients and professional assessment.
The indoor pressure offset is found by bisection on the mass-balance residual. Bisection is bracketed over a wide pressure interval and repeated for a fixed number of iterations. The neutral-plane height follows from the zero of the resulting linear pressure profile. Animation uses a fixed 1/60 s time step; rendering is separate from the model update.