The Building That Breathes
Find the invisible height where indoor and outdoor air pressure balance — and watch the leaks decide which way the building breathes.
The warmer indoor air is lighter. Pressure changes with height, so air enters below the neutral plane and leaves above it.
Set the conditions
Every setting below is illustrative; the physical constants are textbook values.
Find the zero-pressure height
Imagine taking pressure readings at evenly spaced taps up the stairwell. Interpolate the height where indoor and outdoor pressure match, then compare it with the model's neutral plane.
Does the model balance?
MODEL NOTESThe science+
1. Air density sets the pressure gradient
For dry air treated as an ideal gas, density is ρ = p/(RairT). The model uses textbook values p = 101,325 Pa, Rair = 287.05 J kg⁻¹ K⁻¹ and g = 9.80665 m s⁻². Temperatures are converted to kelvin before calculating density.
2. The neutral pressure plane
At the neutral pressure plane, indoor and outdoor static pressures are equal. With constant indoor and outdoor densities, the pressure difference at height z is Δp(z) = pinside − poutside = (ρoutside − ρinside)g(z − zN). The pressure difference is zero at z = zN.
3. Leakage flow and mass balance
Each opening follows the orifice relation |ṁ| = CdA√(2ρ|Δp|). The upstream density is used: outdoor density for inflow and indoor density for outflow. The neutral plane is found by bisection so total inflow mass equals total outflow mass. A closed-form two-opening solution is calculated independently as a check.
4. What is simplified
The building is a single, well-mixed air column with two equivalent leakage openings at 12% and 88% of its height. The floor plate is fixed at an illustrative 80 m². Wind, mechanical fans, door movement, humidity, thermal stratification, internal partitions, transient room pressure and detailed crack geometry are omitted. The flow is quasi-steady; only the tracer animation advances in fixed time steps.
5. Textbook and illustrative values
Gravity, the specific gas constant for dry air, atmospheric reference pressure and the ideal-gas relation are textbook quantities. Building dimensions, temperatures, leakage areas, discharge coefficient and floor area are illustrative inputs, not measurements of a real building. The cutaway is schematic and not to architectural scale.