MYSIMULATOR / SCIENCE FIELD LAB
ENERGY & INFRASTRUCTURE · NATURAL VENTILATION

The Building That Breathes

Find the invisible height where indoor and outdoor air pressure balance — and watch the leaks decide which way the building breathes.

LIVE CUTAWAY

A pressure balance in a tall building

QUASI-STEADY MODEL
NEUTRAL PRESSURE PLANE—illustrative · above ground
STACK PRESSURE SPAN—illustrative · bottom to top
AIR EXCHANGE—illustrative · outside air
AIR CHANGES / HOUR—illustrative · 80 m² floor plate
WHAT YOU ARE SEEING

The warmer indoor air is lighter. Pressure changes with height, so air enters below the neutral plane and leaves above it.

CHANGE THE BUILDING

Set the conditions

Every setting below is illustrative; the physical constants are textbook values.

Render qualityHigh adds more airflow tracers; the physics is unchanged.
FIELD EXPERIMENT

Find the zero-pressure height

Imagine taking pressure readings at evenly spaced taps up the stairwell. Interpolate the height where indoor and outdoor pressure match, then compare it with the model's neutral plane.

Awaiting measurement
101 taps · illustrative measurement · linear interpolation
NUMERICAL CHECKS

Does the model balance?

Reference air density20 °C ideal-gas value vs textbook reference—
Hydrostatic pressureNumerical height-slice sum vs closed form—
Opening mass balanceInflow vs outflow at the solved plane—
Neutral-plane solutionBisection vs two-opening closed form—
Checks compare independent calculations; differences are shown as percentages.
MODEL NOTESThe science+

1. Air density sets the pressure gradient

For dry air treated as an ideal gas, density is ρ = p/(RairT). The model uses textbook values p = 101,325 Pa, Rair = 287.05 J kg⁻¹ K⁻¹ and g = 9.80665 m s⁻². Temperatures are converted to kelvin before calculating density.

2. The neutral pressure plane

At the neutral pressure plane, indoor and outdoor static pressures are equal. With constant indoor and outdoor densities, the pressure difference at height z is Δp(z) = pinside − poutside = (ρoutside − ρinside)g(z − zN). The pressure difference is zero at z = zN.

3. Leakage flow and mass balance

Each opening follows the orifice relation |ṁ| = CdA√(2ρ|Δp|). The upstream density is used: outdoor density for inflow and indoor density for outflow. The neutral plane is found by bisection so total inflow mass equals total outflow mass. A closed-form two-opening solution is calculated independently as a check.

4. What is simplified

The building is a single, well-mixed air column with two equivalent leakage openings at 12% and 88% of its height. The floor plate is fixed at an illustrative 80 m². Wind, mechanical fans, door movement, humidity, thermal stratification, internal partitions, transient room pressure and detailed crack geometry are omitted. The flow is quasi-steady; only the tracer animation advances in fixed time steps.

5. Textbook and illustrative values

Gravity, the specific gas constant for dry air, atmospheric reference pressure and the ideal-gas relation are textbook quantities. Building dimensions, temperatures, leakage areas, discharge coefficient and floor area are illustrative inputs, not measurements of a real building. The cutaway is schematic and not to architectural scale.

Made with 🤖 ChatGPT