When a Building Breathes: The Stack Effect

Explore how temperature and opening height drive natural ventilation—even without a fan.

ILLUSTRATIVE CUTAWAY · PHYSICS-SCALED FLOW
Flow rate · scaled— m³/s
Pressure drive · scaled— Pa
Air changes · scaled— h⁻¹

Three independent numerical checks

Hydrostatic vs density-ratio pressure—
Two-vent network vs effective-area flow—
Air-change identity vs exchange time—

Checks compare independently evaluated equivalent formulations. Their tiny differences validate the arithmetic, not the real-world assumptions.

The science · equations and assumptions

Ideal-gas density: ρ = p/(R T), with p = 101325 Pa, R = 287.05 J/(kg·K), and g = 9.80665 m/s² (textbook constants). The buoyancy pressure across vent separation H is Δp = g H |ρoutside − ρinside|. Equal vents with area A and discharge coefficient Cd have effective area Aeff = A/√2. Volume flow is Q = Cd Aeff √(2 Δp / ρreference), where ρreference = (ρinside + ρoutside)/2. The sign of Tinside − Toutside determines direction. Air changes per hour: ACH = 3600 Q / V. Nominal exchange time: τ = V/Q.

The animated tracers are illustrative and move with a speed scaled to calculated Q. The two-opening, steady-state model assumes a well-mixed room, equal vent sizes, fixed temperatures, constant atmospheric pressure, no wind, no leakage, no thermal feedback, and no internal pressure gradients beyond the stack pressure. It is not a CFD model or a prediction of pollutant clearance. At zero temperature difference, flow is exactly zero and the nominal exchange time is undefined. Numerical checks are algebraic cross-checks, not experimental validation.

No third-party brands or affiliations are represented.