MYSIMULATOR FIELD LAB
BUILDING PHYSICS / NATURAL VENTILATION
INTERACTIVE OBSERVATORY
ENERGY & INFRASTRUCTURE · VENTILATION

The Neutral Pressure Plane

How a building finds its balance between inside and outside air

A warmer interior is less dense. Outdoor air enters low down and warmer air leaves higher up.

CHANGE THE BUILDING

Operating conditions

MEASURE AGAINST THEORY

Stack-flow experiment

Temporarily remove wind, solve the pressure network, and compare its mass flow with the textbook two-opening estimate.

Ready · current controls will be used
MODEL NOTESThe scienceEQUATIONS · ASSUMPTIONS · LIMITS +

Pressure balance

The indoor and outdoor hydrostatic pressure profiles have different slopes when their air densities differ:

Δp(z) = p₀ + (ρₒ − ρᵢ) g z − ½ρₒU²Cₚ

At each opening, the signed mass flow follows the orifice relation:

ṁ = sgn(Δp) Cᵈ A √(2ρᵤ |Δp|)

The unknown reference pressure p₀ is found by bisection until the sum of the opening mass flows is zero. The gravity constant g = 9.81 m/s² and dry-air gas constant R = 287.05 J/(kg·K) are textbook values.

What is simplified

  • One well-mixed indoor zone with two discrete openings; no room-by-room network.
  • Steady pressure balance at each control setting; the moving particles are a visual tracer, not a CFD solution.
  • Constant discharge coefficient and fixed wind pressure coefficients. Their values are illustrative, not building-specific measurements.
  • Dry ideal-gas air at a fixed outdoor reference temperature and atmospheric pressure.
  • Wind pressure is applied at the two openings; turbulence, gusts, sheltering and façade interactions are omitted.

The neutral plane is the reference-facade height where the hydrostatic indoor–outdoor pressure difference is zero. With wind, the actual zero-pressure height can differ between façades.

How to read the exhibit

Positive opening pressure means the model predicts outward flow; negative pressure means inward flow. The neutral plane can move when opening areas change because the mass-balance pressure p₀ changes.

All opening dimensions, weather conditions, discharge and wind coefficients are illustrative. The building drawing and airflow tracers are scaled for legibility; they are not architectural dimensions or a prediction for a real property.

This is an educational single-zone model, not a ventilation design or indoor-air-quality assessment.

FIELD NOTERead the companion article in article.md · seed 583947 is illustrative.
Made with 🤖 ChatGPT