The Neutral Pressure Plane
How a building finds its balance between inside and outside air
A warmer interior is less dense. Outdoor air enters low down and warmer air leaves higher up.
Operating conditions
Stack-flow experiment
Temporarily remove wind, solve the pressure network, and compare its mass flow with the textbook two-opening estimate.
MODEL NOTESThe scienceEQUATIONS · ASSUMPTIONS · LIMITS +
Pressure balance
The indoor and outdoor hydrostatic pressure profiles have different slopes when their air densities differ:
At each opening, the signed mass flow follows the orifice relation:
The unknown reference pressure p₀ is found by bisection until the sum of the opening mass flows is zero. The gravity constant g = 9.81 m/s² and dry-air gas constant R = 287.05 J/(kg·K) are textbook values.
What is simplified
- One well-mixed indoor zone with two discrete openings; no room-by-room network.
- Steady pressure balance at each control setting; the moving particles are a visual tracer, not a CFD solution.
- Constant discharge coefficient and fixed wind pressure coefficients. Their values are illustrative, not building-specific measurements.
- Dry ideal-gas air at a fixed outdoor reference temperature and atmospheric pressure.
- Wind pressure is applied at the two openings; turbulence, gusts, sheltering and façade interactions are omitted.
The neutral plane is the reference-facade height where the hydrostatic indoor–outdoor pressure difference is zero. With wind, the actual zero-pressure height can differ between façades.
How to read the exhibit
Positive opening pressure means the model predicts outward flow; negative pressure means inward flow. The neutral plane can move when opening areas change because the mass-balance pressure p₀ changes.
All opening dimensions, weather conditions, discharge and wind coefficients are illustrative. The building drawing and airflow tracers are scaled for legibility; they are not architectural dimensions or a prediction for a real property.
This is an educational single-zone model, not a ventilation design or indoor-air-quality assessment.