Warm indoor air is lighter: low-level openings tend to admit air, while upper openings tend to exhaust it.
Integrate the strongest opening’s airflow over a fixed test interval, then compare the measured volume with the steady-flow prediction.
The science MODEL NOTES
Governing equations
Air density: ρ = p / (RdT), using the ideal-gas approximation at fixed barometric pressure.
Stack pressure: Δps(z) = p0 + gz(ρout − ρin). The pressure offset p0 is found by solving whole-building mass balance.
Wind pressure: Δplocal = Δps − ½ρoutV²Cp. The two façades use illustrative pressure coefficients.
Opening flow: ṁ = sign(Δp) CdA√(2ρup|Δp|). Positive flow is outward; negative flow is inward.
Neutral plane: zn = −p0 / [g(ρout − ρin)], when the temperature difference creates a meaningful stack gradient.
What is simplified
The tower is represented as one well-mixed pressure zone with a fixed outdoor temperature and a fixed indoor–outdoor temperature difference. It has a scaled set of twelve storeys, two façade leak paths per storey, and an optional ground-level opening.
Leak paths behave as sharp-edged orifices. The discharge coefficient and wind pressure coefficients are representative modelling choices, not measurements of a particular building. Wind is steady and acts on two opposing façades.
The pressure field is solved algebraically at each control change. Airflow tracers are visual particles advanced with a fixed time step; they illustrate direction and relative flow, not individual molecules. The building’s temperature, moisture, room-to-room transfer, fan systems and time-varying gusts are not simulated.
Labels: “textbook” marks standard physical constants or reference values; “illustrative” marks chosen assumptions and model settings; “scaled” marks the displayed building and computed scene quantities.