Governing equation
The steady temperature field satisfies ∇·(k∇T) = 0. Heat flux follows Fourier’s law, q = −k∇T. The model solves this equation on a two-dimensional cross-section using a conservative finite-volume stencil with harmonic conductivity at material interfaces.
Boundary conditions
Room and outdoor air exchange heat with the two wall faces through Robin conditions: q″ = h(Tair − Tsurface). The illustrative film coefficients are 7.7 W/(m²·K) indoors and 25 W/(m²·K) outdoors. The top and bottom edges of the model are adiabatic.
Materials and dimensions
The wall contains inner masonry (0.72 W/(m·K)), insulation (0.036 W/(m·K)) and outer brick (0.77 W/(m·K)). The slab conductivity is adjustable; a thermal-break insert is represented by 0.18 W/(m·K). These are illustrative representative values, not a product specification.
Textbook, illustrative and scaled values
Fourier’s law, steady energy conservation and series resistance are textbook relationships. Material conductivities, film coefficients, dimensions and the dew-point screen are illustrative. The colour field and cross-section drawing are scaled for display.
What is simplified
This is a steady, two-dimensional, metre-wide slice. It excludes moisture transport, radiation, thermal storage, fasteners, reinforcement, contact resistance, wind pressure and three-dimensional edge effects. The balcony overhang is drawn for context; the computational domain ends at the exterior wall face. The slab and insert are idealised as continuous rectangular regions.
What is illustrative
Material conductivities, surface film coefficients, the simplified slab geometry and the dew-point screen are illustrative. The dew point uses the Magnus approximation and indicates possible surface condensation conditions only; it is not a mould prediction or building assessment.
An independent educational model; not affiliated with any building-material manufacturer or certification body.