Chimney Draft & the Neutral Pressure Plane

Warm air can ventilate a building without a fan. Change the geometry and temperature, then watch where the air enters, leaves, or stops.

● LIVE SIMULATIONHIGH QUALITY
ILLUSTRATIVE CUTAWAY · NOT TO SCALE0.0 s · scaled
VOLUME FLOW · textbook model—
STACK PRESSURE · textbook model—
NEUTRAL HEIGHT · textbook model—
AIR SPEED · textbook model—
MODEL VALIDATION

Three independent checks

LIVE · % DIFFERENCE

Textbook: ideal gas density and steady orifice-flow equations. Illustrative: room cutaway, moving tracers, perfect mixing and the fixed-volume exchange experiment. All percentages compare two independently calculated forms of the stated model, not experimental accuracy.

The science Equations, assumptions and limits +

What drives the flow?

Air density is calculated from the ideal gas law: ρ = p / (R T), with p = 101325 Pa and R = 287.05 J kg⁻¹ K⁻¹. The stack pressure over height H is Δp = g H (ρoutside − ρinside), with g = 9.80665 m s⁻².

For two vents with discharge coefficient C and areas Aₗ and Aᵤ, the steady flow magnitude is Q = C √(2 |Δp| / (ρinside/Aᵤ² + ρoutside/Aₗ²)) for upward flow. For downward flow the inlet and outlet densities swap accordingly. This is a simplified two-orifice Bernoulli balance.

The neutral plane is the height where the indoor and outdoor static pressures match. For upward flow, zₙ = [ρoutside (Q/(C Aₗ))² / 2] / [g (ρoutside − ρinside)]. For reverse flow the upper opening supplies the inflow and the formula changes accordingly.

What is simplified?

Temperatures are uniform, vents are thin orifices, pressure is hydrostatic, and flow is steady and incompressible through each vent. No wind, fan, heat transfer, turbulence resolution, duct friction, or transient thermal stratification is modelled. The arrows are visual tracers, not individual air molecules. Neutral height is undefined at exactly zero buoyancy; the display then marks it as not defined.

The numerical bisection check solves the opening pressure balance without using the closed-form flow equation. The mass check compares both vent volume fluxes; the pressure check reconstructs the total pressure drop from the two orifice losses. A small percentage difference establishes arithmetic consistency, not validation against a real building.