Capillary Heat Pipe

The wick that moves heat — without a pump.

MODELCAPILLARY
LIMIT
STEADY-STATE · WATER
LIVE CUTAWAY
CAPILLARY RESERVE HEALTHY
vapour · outward liquid · return latent heat DRAG TO INSPECT

Heat evaporates water at the hot end. Vapour travels through the open core, condenses at the cold end, and the wick draws liquid back.

MEASURE IT

Find the capillary limit

Increase the trial heat load until the calculated liquid, vapour and gravity pressure losses use the available meniscus pressure. A bisection search measures the threshold independently of the closed-form expression.

MEASURED THRESHOLD—Run the experiment to compare with theory.
NUMERICAL INTEGRITY

Independent checks

✓
Meniscus curvatureLaplace pressure vs. two-radius curvature
0.00%
✓
Porous-wick pressureDarcy law vs. finite-cell integration
0.00%
✓
Latent-heat ledgerMass flow reconstructed from enthalpy
0.00%
✓
Limit closurePressure balance at the solved threshold
0.00%
All differences are computed live. Illustrative numerical target: below 0.01%.
REFERENCE DESKThe science+

How the heat pipe works

A sealed heat pipe contains a small amount of working fluid and a porous lining called a wick. Heat supplied at the evaporator turns liquid into vapour. The vapour moves through the open core toward the cooler condenser, releases latent heat, and becomes liquid again. Curved menisci in the wick create capillary suction that returns the condensate.

The wick is both a pump and a porous flow resistance. Smaller pores create stronger suction, but a fine porous structure often has lower permeability. The useful design is a balance between capillary pressure and the pressure losses needed to circulate liquid and vapour.

Equations used

ΔPcap = 2 σ cos θ / rp
ΔPl = μl L Q / (K Aw ρl hfg)
ΔPv = 8 μv L Q / (π rv4 ρv hfg)
ΔPg = ρl g L sin α
Qcap = max[0, (ΔPcap − ΔPg) / (Cl + Cv)]

What is simplified

The model uses saturated water properties at a fixed 60 °C, a constant contact angle, a uniform wick cross-section, Darcy flow for the liquid, and laminar Poiseuille flow for vapour at a fixed reference density. The wick thickness is fixed at 0.55 mm. The elevation term is positive when the evaporator is above the condenser.

This is a steady capillary-limit model, not a full heat-pipe design code. It omits transient startup, non-condensable gases, sonic, boiling and entrainment limits, local hot spots, and detailed two-phase interfacial effects. The calculated capillary ceiling is therefore not a guarantee of a real device's maximum power.

Number labels: water properties are textbook reference values; slider settings and geometry are illustrative; animation timing and visual particle density are scaled. No external data or network services are used.