THE VERTICAL PRESSURE FIELD

Building Stack Effect

Follow the air. Find the neutral plane.

IDEAL GAS + ORIFICE MODEL
SECTION A—A · ILLUSTRATIVE
DRAG TO PAN · SCROLL TO ZOOM
Airflow path
Neutral pressure plane
Opening
All geometry is illustrative
i
WHAT YOU ARE SEEING

Warm indoor air is less dense. Outdoor air enters low down and leaves through the upper opening.

LIVE MEASUREMENTS
Computed from the current pressure balance · illustrative model
VENTILATION FLOW ILLUSTRATIVE
0.00 m³/s
Through-flow across both openings
STACK PRESSURE SPAN ILLUSTRATIVE
0.0 Pa
Buoyancy head between openings
NEUTRAL PLANE ILLUSTRATIVE
— m
Windward façade · above ground
AIR CHANGES ILLUSTRATIVE
0.00 h⁻¹
Assumes a 420 m² floor plate
MODEL INTEGRITY

Independent checks

LIVE
✓
Mass continuityInflow and outflow balance at steady state
0.000%residual · scaled
✓
Closed-form pressure balanceBisection root against the two-opening analytic solution
0.000%difference · scaled
✓
Dry-air density referenceIdeal-gas result at 20 °C and 101.325 kPa
0.00%difference · textbook
The checks test conservation, an independent algebraic solution, and a published reference condition. They are recalculated as the controls move.
MEASURE IT

Opening flow test

⌁

Collect a virtual 0.50 m³ air sample through the active opening. The timer integrates the model flow, then compares the measured rate with the pressure-law prediction.

SAMPLE COLLECTED ILLUSTRATIVE0.00 / 0.50 m³
Ready to measure0.00 s
MEASURED FLOW— m³/s
THEORY FLOW— m³/s
DIFFERENCE— %
FIELD GUIDEThe science+

Why does a building breathe?

Air pressure changes with height. Warm indoor air is less dense than cold outdoor air, so their hydrostatic pressure gradients differ. The pressure difference changes sign at a neutral pressure plane: below it, the building tends to draw air in; above it, air tends to flow out. Wind can shift or reverse those flows.

IDEAL-GAS DENSITY
ρ = p / (R T)
p = 101,325 Pa · R = 287.05 J/(kg·K)
PRESSURE DIFFERENCE
Δp(z) = C + g(ρₒ − ρᵢ)z − Cₚqᵥ
qᵥ = ½ρₒV² · Δp positive means outward
OPENING FLOW
Q = Cᵈ A sgn(Δp) √(2|Δp| / ρ)
ρ is the density on the side the air enters from
STEADY MASS BALANCE
Qₗ + Qᵤ = 0
The internal pressure offset C is solved by bisection

What is simplified?

The building is represented by two openings at 12% and 88% of its height. Each opening has a uniform effective area and discharge coefficient. Indoor and outdoor air are treated as dry, ideal, well-mixed columns at constant temperature. The model solves a steady pressure balance; it does not calculate room-by-room temperatures, leakage paths, turbulence, transient gusts, or detailed façade pressure distributions.

What is illustrative?

Building dimensions, opening areas, wind coefficients (+0.60 and −0.30), floor-plate area, presets, and the visual airflow are illustrative. The model uses textbook values for gravity, the dry-air gas constant, and atmospheric reference pressure. Live readouts are calculated from the simplified equations, not measured building performance.

Educational engineering model · not a building design or compliance tool.