Opening the classroom…
🏫 Classroom air controls
The science

Model. The room (V = 168 m³) is treated as one well-mixed box. Infectious "quanta" (Wells-Riley: one quantum is the dose that infects 63 % of susceptibles) are emitted at S = I q (1 − ηe) per hour and removed at a total first-order rate λ = ACH + CADR/V + ksettle + kinact. Then dC/dt = S/V − λC, so C(t) = S/(Vλ) (1 − e−λt).

Risk. A susceptible breathing p (1 − ηi) m³/h inhales dose D = p(1−ηi)∫C dt and is infected with probability P = 1 − e−D (Wells-Riley). With only ventilation and a long stay this reduces to the Rudnick-Milton form D = I q p t / Q. Expected new cases = (N − I) P.

CO₂. dc/dt = N g/V − ACH (c − cout); steady state cout + 1000 N g / Q ppm (g in L/h per person, Q in m³/h). CO₂ is a ventilation proxy only: HEPA filters remove aerosol but not CO₂.

The cloud. Orange dots are a Lagrangian cloud: each is created at the infectious student's mouth at a Poisson rate and removed with hazard λ, so their count obeys the same ODE as the box model (see the chart). Where they wander is an illustrative convection cell plus a random walk, not CFD; real rooms have local plumes, so the box model is a room average, not a seat-by-seat prediction.

Illustrative parameters (not measurements). Quanta rates q = 2 / 10 / 40 per hour (breathing / talking / loud), breathing 0.4 / 0.5 / 0.7 m³/h, mask efficiencies, HEPA 250 m³/h per unit and ksettle = 0.24 /h are round figures in the range of published studies; kinact = 0.63 /h corresponds to the ~1.1 h aerosol half-life reported for SARS-CoV-2 (van Doremalen et al., 2020). Real values vary by pathogen, variant and person by an order of magnitude or more. This is a physics illustration, not medical or health advice.

Honest simplifications. Perfect mixing, constant emission, no re-suspension, no deposition on surfaces other than the single settling rate, identical susceptibles, no immunity, one room with no door traffic; masks use a single efficiency each.

Independent checks (run on load, same core as the 2D page):

running…

Lesson clock

Time into lesson-
Removal rate λ (ACH, HEPA, settle, decay)-
Outdoor air per person-
CO₂ now-
Airborne quanta in room-
Risk per student, now-
Risk at end of lesson-
Expected new cases-
Cloud particles vs box model-
box model C(t)particle count
risk at end of lesson vs air changes (yellow dot: you)
-
Drag to orbit, pinch or scroll to zoom. A red ring marks the infectious student. Illustrative physics, not health advice.
Made with 🟠 Blender · Three.js