When a Building
Breathes

Warm air rises. A building can ventilate itself without a fan—but only when the pressure and openings cooperate.

LIVE PHYSICS ● RUNNING
SECTION THROUGH A BUILDINGILLUSTRATIVE · 0.0 s
Indoor airOutdoor airNeutral plane

LIVE INSTRUMENTS · ILLUSTRATIVE MODEL
Volume flow—m³/s · illustrative
Pressure difference—Pa · illustrative
Neutral height—m · illustrative
Indoor temperature—°C · illustrative

Three independent checks

Differences compare independent numerical or analytical methods, not measurements from a real building.

The science Equations, assumptions & limitations +

Hydrostatic pressure and buoyancy

Ideal-gas density: ρ = pₐ/(R T), with pₐ = 101,325 Pa and R = 287.05 J/(kg·K). The indoor–outdoor pressure difference at height z is Δp(z) = Δp₀ + g(ρₒ − ρᵢ)z. The neutral plane satisfies Δp(zₙ) = 0.

Flow through the openings

At each opening, signed mass flow into the building is −Cᵈ A sign(Δp) √(2ρ|Δp|), with Cᵈ = 0.62 (illustrative). The indoor reference pressure Δp₀ is found by bisection so inflow and outflow mass rates balance. The plotted volume flow is mass flow divided by outdoor density.

Temperature evolution

In the illustrative well-mixed room, dTᵢ/dt = [Q + ṁ cₚ(Tₒ−Tᵢ) − U(Tᵢ−Tₒ)]/(ρᵢ V cₚ), with cₚ = 1005 J/(kg·K), U = 100 W/K, and V = 120H m³. A fixed 0.05 s RK4 step integrates this equation; airflow is recalculated within each stage. The experiment freezes temperature to isolate the height law.

What is simplified?

Air is ideal, indoor air is uniformly mixed, opening discharge coefficients are fixed, and wind, turbulence, shafts, internal doors, humidity, fans and compressibility transients are omitted. The building is a conceptual cross-section, not an engineering design. Geometry, tracer particles and colour are illustrative; physical constants are textbook values. The calculations are educational, not a ventilation safety assessment. No brand affiliation.