Transmission Line Loss: Voltage, Distance and Conductor Heating

Blender lattice pylons carry three conductors; the wires glow as Joule heating grows and the energy dots dim along the line. Drag to orbit.

Switch to 2D
Controls

Presets

Parameters

Quality

Camera

Model checks

The science

Why high voltage. A line must deliver power P. At voltage V the current is I = P/(√3 V cosφ) (three-phase AC) or I = P/(2V) (bipolar DC), and the conductors turn I2R into heat: Ploss = 3 I2R (AC) or 2 I2R (DC). With R = ρL/A the loss share scales as P L /(V2 A cos2φ): doubling the voltage cuts it to a quarter, doubling the line doubles it.

Model. Aluminium, ρ = 0.0282 Ω mm²/m, series reactance 0.35 Ω/km for AC. The receiving end is held at nominal voltage and the sending end is found from the phasor equation Vs = Vr + I (R + jX); the load follows f(h) = 1 + a sin(2π(h−9)/24), so loss follows f² and the daily loss energy is Ploss,0·24·(1 + a²/2): heavier peaks cost more than the average suggests.

Simplifications. Short-line (series) model: no shunt line charging, corona, skin effect, temperature dependence of resistance, or transformer and converter-station losses (HVDC terminals cost roughly 1 to 2 % each in real schemes, which is why HVDC wins only on long lines). Ratings, sag and clearances are not modelled. Checks: sending-end minus receiving-end power against I²R; scaling laws; trapezoid integral against the closed form; voltage drop against its second-order bound.