Heat Pump vs Gas Boiler: One Winter Day of COP, Heat Loss, Cost and CO2 Blender 5.2

A cutaway house with an outdoor unit and a refrigerant loop. Outdoor temperature swings through the day, insulation sets the heat loss, and the pump's COP is a fraction of the Carnot limit.

Presets

Heating system shown

Weather

House

Heat pump

Energy prices and carbon

Today (selected system)

Temperatures

OutdoorIndoorFlow temperature

COP over the day

Real COPCarnot limitDefrost penalty

Power (kW)

Heat loss UA(Ti-To)Heat deliveredElectricity inGas in

Self-checks

Same house, same weather, same day: both systems are simulated side by side.

Daily cost by insulation level

Heat pumpGas boiler

Daily CO2 by insulation level

Experiment 1: at what outdoor temperature does the heat pump stop being cheaper?

Sweeps the mean outdoor temperature from -12 to +14 C with everything else as set now. It finds the crossover where a day on the heat pump costs the same as a day on gas, and compares it with the closed-form root of eta2 · Th/(Th - Tc) = price ratio.
Heat pump cost / dayGas cost / day
Press the button.

Experiment 2: how big should the heat pump be?

Sweeps the rated output (kW at +7 C) on this weather and finds the smallest size that needs no backup heater, against the analytic size for the coldest hour.
Backup heater kWh / dayCost / day (GBP)Mean COP
Press the button.
The science

Why a heat pump delivers more heat than the electricity it uses

A heat pump moves heat from cold outdoor air to the warm house with a compressor. By the first law the heat delivered is Qh = Qc + W: the heat taken from the air plus the work of the compressor. The ratio COP = Qh / W is typically 2.5 to 4.5, so one kWh of electricity gives 3 or more kWh of heat. A gas boiler cannot exceed 1 kWh of heat per kWh of fuel (about 0.89 for a condensing boiler in real use).

The Carnot ceiling and the second-law efficiency

No machine can beat the reversible limit COPCarnot = Th / (Th - Tc), with temperatures in kelvin. Here Th = Tflow + 2 K (condenser approach) and Tc = Tout - 5 K (the evaporator must be colder than the air). Real units reach a fraction eta2 of it (default 0.5): COP = eta2 · Th/(Th - Tc) · (1 - pdefrost). At +7 C outdoors and 35 C flow this gives about 4.4, in the range of published figures.

Why a colder day or hotter radiators hurt

The lift Th - Tc grows when the outdoor air is colder or the water must be hotter. At -5 C with 55 C radiators the lift is about 67 K and the COP falls to about 2.5; underfloor heating at 35 C needs only 47 K and gives about 3.3. Weather compensation lowers the flow temperature on mild days: Tflow = Tset + (Tdesign - Tset) (Q/Qdesign)1/1.3, using the radiator exponent 1.3.

Defrost

Below about 5 C humid air freezes onto the evaporator. The unit must periodically reverse the cycle (or heat the coil) to melt the ice, which costs energy and interrupts heating. The model uses a penalty that peaks near +1.5 C in very humid air (up to 15 %) and vanishes in dry or warmer air; it is an average, not a cycle-by-cycle model.

The house

One-node model: C dTi/dt = Qheat + Qgains - UA (Ti - To), solved exactly over each 5-minute step with tau = C/UA. UA (W/K) is the heat-loss coefficient: 320 uninsulated, 240 with loft insulation, 160 with wall insulation too, 85 for a full retrofit. The thermostat asks for UA(Tset - To) - gains plus a recovery term. Heat pump capacity falls with the outdoor temperature, Q = Qrated(1 + 0.025 (To - 7)); any shortfall goes to the optional 6 kW resistive backup at COP 1, or the house cools.

Cost and carbon

Running cost = electricity kWh x price + gas kWh x price. CO2 = electricity kWh x grid intensity + gas kWh x 0.184 kg/kWh. The heat pump is cheaper to run only when its COP exceeds priceelec x etaboiler / pricegas; it emits less CO2 when its COP exceeds Igrid x etaboiler / 0.184. Prices and grid intensity are illustrative round numbers, not any supplier's tariff.

Independent numerical checks

  • Energy balance: the delivered-power schedule is re-integrated with a 1-second explicit Euler loop; heat in plus gains minus loss must equal the stored change, and the Euler heat loss must match the exact-step day.
  • Second law: for the current COP, Qh = Qc + W exactly and entropy generation Qh/Th - Qc/Tc ≥ 0; for eta2 = 1 it is zero (reversible).
  • Break-even: the closed-form crossover temperature equals a numerical bisection of the COP model without defrost.

Simplifications

  • Hot water, cooling, solar gains, wind and occupancy are not modelled; gains are a constant 350 W.
  • Capacity and COP use smooth correlations, not manufacturer maps; compressor modulation limits and cycling losses are ignored.
  • Boiler efficiency is constant; a real condensing boiler gains a few percent with low return temperatures.
  • Heat-loss shares by element (roof, walls, glazing) are shown as an animation only; UA is a single number per insulation level.
  • The refrigerant loop board is schematic: colours show phase and pressure side, not a real P-h calculation. The model is generic and not tied to any manufacturer.