Heat Pump Coil Frosting: Optimal Defrost Interval and Cycle COP

A house with an outdoor heat-pump unit: frost grows on the coil face, the fan slows, and defrost melts it with a puff of steam. Drag to orbit.

Switch to 2D
Controls

Presets

Parameters

Quality

Camera

Model checks

The science

Why the coil frosts. In heating mode the outdoor coil runs colder than the air. When its surface is below 0 °C and the air carries more water vapour than saturated air at the coil temperature, vapour deposits as frost at a rate r0 = kair (ωair - ωice(Tcoil)). Humidity ratios come from the Magnus saturation pressures (over water for the air, over ice for the coil). The worst frosting is near 0 to 5 °C with high humidity: warm enough to be wet, cold enough for the coil to be below freezing.

Capacity decay. Frost blocks the air path, so airflow and heat pick-up fall as the layer grows: dm/dt = r0(1 - m/mc), which gives m = mc(1 - e-t/τ), τ = mc/r0, and a capacity Q = Q0 e-t/τ at constant compressor power. A reverse-cycle defrost of duration td melts the frost using heat drawn from the building: E = mf(Lf + cice|Tc|)/ηd, with ηd = 0.4 of that heat actually melting frost.

Optimum interval. The cycle COP is [Q0τ(1 - e-T/τ) - E(T)] / [P0(T + td)]. Defrosting too often wastes heat on defrosts, too rarely runs on a blocked coil; the best interval satisfies H'(T)(T + td) = H(T): the marginal net heating rate equals the average.

Checks. Golden-section optimum against bisection on the stationarity condition; RK4 frost growth against the closed form; saturation pressures against published tables; and the second-law bound on the clean-coil COP.

Simplifications. Constant compressor power and constant air mass flow when clean, a lumped coil, linear airflow blockage, a fixed defrost efficiency, no frost density change, no fan or indoor-side dynamics, and a single capacity-versus-temperature slope. Numbers are representative, not those of a product.