The science
The duck curve. Solar output follows the sun, load follows people. The grid operator sees the net load that conventional plants must cover:
P_net(t) = P_load(t) - P_solar(t) - P_wind(t)
With a lot of solar, P_net sags around noon and then rises very fast when the sun sets just as evening demand peaks - the neck of the "duck" (named in a 2013 California ISO study of its daily net load). The sag can touch a must-run floor (12 % of peak here), where extra solar is curtailed. Load, solar and wind shapes are smooth illustrative curves, not data of any real grid; solar is scaled so it supplies the chosen share of daily energy, wind a fixed 8 %. The price follows the net load, 12 + (P_high - 12) u^1.6, with u the net load scaled between its day minimum and maximum.
The battery. Power rating P (MW) limits charging and discharging, energy E (MWh) sets the store, and the state of charge is kept between 10 % and 90 %. The round-trip efficiency eta is split evenly, each way sqrt(eta): the store loses P dt / sqrt(eta) when delivering P dt to the grid and gains P dt sqrt(eta) when drawing P dt. Power electronics respond in a fraction of a second, so ramp rate is unlimited at the 5-minute dispatch step and a 0.2 s lag in the frequency model.
Arbitrage. Buy when the price is low, sell when it is high. The schedule is the exact optimum of a dynamic program over 240 state-of-charge levels in 15-minute steps, starting and ending the day at 25 %: V_t(e) = max_k [ price_t * grid energy(k) - c |k| + V_t+1(e + k delta) ], with a throughput cost c = 4 per MWh delivered (degradation and wear, illustrative). Losses mean a price spread must exceed about 1/eta - 1 before cycling pays.
Peak shaving. The battery discharges whenever P_net exceeds a cap and recharges whenever the net load is below it, never pushing the net load above the cap. The grid-side energy needed is
E_grid = integral of ( P_net(t) - P_cap )+ dt (largest contiguous excess)
and the nameplate size follows as E = E_grid / ( sqrt(eta) (SOC_max - SOC_min) ). This assumes the battery can recharge between separate excesses and that its power rating is at least max(P_net) - P_cap. The utility benefit is a demand charge, taken as 12 per kW-month (illustrative) on the reduced peak.
Frequency regulation. A single-area swing equation describes how imbalance moves system frequency. With S the online synchronous rating (1.3 x peak load here), H the inertia constant (s) and a generation loss P_trip:
(2 H S / f0) d(df)/dt = P_gov + P_bat - P_trip - D P_L df / f0
RoCoF, the initial rate of change of frequency, is -f0 P_trip / (2 H S). At the instant of the trip the deviation is zero, so only inertia responds: the battery does not change the initial RoCoF unless it provides synthetic inertia (not modelled). Governors then act through a droop R_g = 5 % and a 4 s lag, T_g dP_gov/dt = -(S_g / (R_g f0)) df - P_gov, limited to 20 % of S, with S_g = 60 % of S on droop. The battery follows a fast droop P_bat = -(P_rated / (R_b f0)) (df - deadband), clamped to its rating, with a 15 mHz deadband and 0.2 s lag. Load damping D = 1 %/% lowers demand slightly as frequency falls. The nadir is the minimum of f(t): the battery lifts it by supplying power during the seconds before governors catch up. Equations are integrated with fourth-order Runge-Kutta, 10 ms step. Load shedding, which real grids start near 48.8 Hz, is not modelled.
Closed form. Without governor, lag or deadband and with the battery unsaturated, the swing equation is linear: df(t) = -(P_trip / K)(1 - e^(-t/tau)) with K = D P_L / f0 + P_rated / (R_b f0) and tau = 2 H S / (f0 K). If the battery saturates at df = P_rated / K_b, the solution continues as a second exponential towards (P_rated - P_trip) f0 / (D P_L). Experiment 2 compares this exact solution with the simulation. The inertia option uses an illustrative H_eff = H (1 - 0.6 s), where s is the solar plus wind share of load at the event hour (at most 0.8), showing why sunny hours carry a larger RoCoF.
Wear and money. A full equivalent cycle is a throughput of one usable window of energy (0.8 E); capacity fade is taken as 0.01 % per cycle (about 20 % after 2000 cycles). Frequency response earns a capacity payment, taken as 14 per MW per hour (illustrative); it is shown as a separate value because that power is not free to arbitrage at the same time.
What the 3D scene shows. Up to 60 generic containers; for larger plants each container stands for more MWh (shown in the legend). Container lights are amber when discharging, blue when charging and green when idle; the share of lit containers is the state of charge. Orange, yellow and blue-white particles are battery, solar and grid power flows; the town lights follow load; turbines turn with the wind profile. Publicly reported grid batteries use containers of roughly 3 to 4 MWh each; the shapes here are generic.
Sources and simplifications. Kundur, Power System Stability and Control (1994), for the swing equation and governor droop; California ISO, What the duck curve tells us about managing a green grid (2013); fast frequency response from batteries has been publicly reported on several grids (for example a 100 MW system in South Australia, 2017). Not modelled: network congestion, transformer limits, voltage, temperature, calendar ageing, reserve markets, forecast errors, inverter current limits during faults, black start and islanding. All parameters are illustrative.