Grid Inertia and RoCoF: Frequency Nadir as Inverter Share Grows

Synchronous generators with spinning flywheel rotors on the left, wind turbines on the right; the tower in the middle is the grid frequency. Drag to orbit.

Switch to 2D
Controls

Presets

Parameters

Quality

Camera

Model checks

The science

Swing equation. The spinning rotors of synchronous generators store kinetic energy. When generation ΔP is suddenly lost, the grid frequency falls at first at the rate RoCoF = −ΔP f0 / (2H), where H is the inertia constant (seconds of full-load energy stored). In per unit: 2H dw/dt = Pg + Pf − ΔP − D w with w = (f − f0)/f0 and load damping D = 1.

Why renewables matter. Wind, solar and batteries connect through inverters that follow the grid and store no rotating energy, so only the synchronous share 1 − s carries inertia: H = Hs(1 − s), Hs = 5 s. With less inertia the same trip gives a faster fall and a deeper nadir. Governors then raise output by −(1 − s) w / R through a turbine lag tg and limited by the spinning reserve; optional fast frequency response from inverters injects power 0.5 s after the frequency is 0.2 Hz low. With unlimited reserve the settled deviation is −ΔP/(D + (1 − s)/R).

Simplifications. One-bus (single-area) model, linear load damping, first-order governor and FFR, no inter-area oscillations, no inverter grid-forming control or limits, constant inertia constant, and the lost unit is assumed not to change H. Thresholds 1 Hz/s and 49 Hz are typical examples, not those of one grid. Checks: initial slope against the analytic RoCoF; the exact exponential without governors; explicit Euler against RK4; and the closed-form settled frequency.

Loading model...
Loading Blender model...
-
-
Made with 🟠 Blender · Three.js