Moisture reaching a cold surface
Ambient vapour density follows ρᵥ = pᵥ/(RᵥT). When the coil surface is below freezing, the deposition flux is approximated by ṁ = hₘA max(0, ρᵥ,air − ρᵥ,sat,ice).
Heat transfer through the coil
Air, frost and refrigerant-side resistances act in series: R = 1/(hA) + δ/(kᶠA) + 1/(UᵣA). The surface balance is (Tₐ − Tₛ)/Rₐ + ṁLₛ = (Tₛ − Tₑ)/(Rᶠ + Rᵣ).
Frost blocks the air path
Frost thickness grows as dδ/dt = ṁ/(ρᶠA). The open fraction is φ = max(0.18, 1 − 2δ/g); fan flow scales with fan·√φ and the air-side coefficient with airflow to the illustrative 0.65 power.
Heating performance
The displayed heating COP is an illustrative fraction of the Carnot limit, COPₕ = 0.42·Tₕ/(Tₕ − Tₑ). During defrost, melt energy per mass is Lᶠ + cᵢce(0 − Tᶠ). It is not a compressor-map prediction.
What is simplified
- One uniform frost layer covers a fixed effective coil area; frost density and conductivity are illustrative constants.
- The coil surface is treated as quasi-steady. Airflow and heat transfer use compact engineering correlations.
- Refrigerant distribution, fin-by-fin temperature variation, drainage, frost shedding and compressor transients are not resolved.
- Defrost is an idealised reverse-cycle heat input with a fixed efficiency and power.
Physical constants are labelled textbook; geometry, operating maps and fitted coefficients are illustrative. This is an educational model, not a design or performance guarantee.
No affiliation with any heat-pump manufacturer or brand.