FFIELD LAB / THERMAL SYSTEMS
LIVE MODEL
OUTDOOR UNIT / EVAPORATOR

Frost Fronts

RUNNING · HEATING MODE
AIRFLOW FROST HEAT TRANSFER

Water vapour diffuses towards sub-zero fin surfaces and freezes. The growing layer narrows the air passages.

FROST LAYER ILLUSTRATIVE
0.00 mm
ON FIN SURFACE
AIRFLOW RETAINED ILLUSTRATIVE
100 %
CLEAN-COIL REFERENCE
COIL HEAT FLOW ILLUSTRATIVE
— W/m²
AIR + DEPOSITION LATENT HEAT
PRESSURE DROP ILLUSTRATIVE
— Pa
ACROSS FIN BANK
EXPERIMENT SETUP

Operating conditions

All operating values, thresholds and simulated times are illustrative; reference constants are marked textbook. Slider ranges are not equipment ratings. The model represents one square metre of coil face.
TEST RIG

Run the experiment

ELAPSED · ILLUSTRATIVE00:00
Automatic defrostTrigger when the fin passages reach the model threshold
Render qualityHigh detail by default; low mode reduces drawing work
MEASUREMENT
10-minute frost-rate test

Run a separate fixed-condition trial and compare the measured average deposition rate with the initial mass-transfer prediction.

Awaiting measurement · illustrative model
MODEL INTEGRITY

Independent checks

3 CHECKS · LIVE
Saturation pressure at 0 °C TEXTBOOK
0.611 kPa · 0.0% difference
Buck saturation relation vs reference 0.611 kPa
Fusion energy for 1 g ice TEXTBOOK
334 J · 0.0% difference
Model latent heat vs reference 334 J per gram
Frost mass ledger ILLUSTRATIVE
0.00% · residual
Initial mass + deposited − melted − remaining
MODEL NOTESThe science+

Governing relations

Ambient vapour pressure is estimated from relative humidity and the Buck saturation-pressure relation. Vapour density follows the ideal-gas relation, ρᵥ = pᵥ/(RᵥT). For a sub-zero fin, the deposition flux is j = hₘ max(0, ρᵥ,air − ρᵥ,surface). Frost mass per frontal area advances with dm/dt = j − ṁₘₑₗₜ.

Frost thickness is δ = m/ρf. The open fraction of the fin passage is approximated by φ = max(0.08, 1 − 2δ/s), where s is fin spacing. A simple fan/system curve gives face velocity v = v₀φ³ᐟ² and pressure drop Δp = Δp₀/φ³.

Defrost and heat flow

Sensible heat transfer uses qₛ = h(Tair − Tcoil); deposition contributes latent heat qₗ = jLsub. Defrost melt rate is limited by available heater or reverse-cycle heat: ṁₘₑₗₜ = qdefrost/[Lf + cp,ice max(0, −Tcoil)]. The model uses a fixed two-second integration step.

Textbook constants include Rᵥ = 461.5 J kg⁻¹ K⁻¹, Lsub = 2.834 MJ kg⁻¹ and Lf = 334 kJ kg⁻¹. Frost density, heat-transfer correlations, fan curve, defrost heat input and the one-square-metre reference area are illustrative assumptions, not a calibrated product model.

What is simplified

The coil is represented by one average surface temperature and a uniform frost layer. Local fin geometry, droplet runback, meltwater drainage, frost porosity evolution, refrigerant distribution, compressor controls, transient metal heat capacity and detailed psychrometric boundary layers are not solved. Relative humidity is interpreted against liquid-water saturation for the ambient-air input. Frost density remains fixed so thickness and blockage are transparent.

How to interpret it

Use the presets to compare dry air, humid near-freezing air, deep-cold conditions and a deliberately blocked coil. The rate test is a controlled numerical experiment, not a field measurement. All operational outputs are illustrative; reference constants and textbook checks are labelled separately.