MY SIMULATOR · ENERGY SYSTEMS
Cold-load pickup
A distribution-feeder restoration observatory
RESTORATION LIVE
0 min · illustrative
Real power
0.0kW
ILLUSTRATIVE
Transformer loading
0%
ILLUSTRATIVE · APPARENT / RATING
Feeder current
0.0A
11 kV · ILLUSTRATIVE
Top-oil temperature
0.0°C
ILLUSTRATIVE · THERMAL PROXY

When power returns, cold buildings call for heat together. Watch the aggregate demand and transformer loading evolve.

0 / 96HEATING CALLS · SCALED
CONTROLLED EXPERIMENT
Measure the first-hour pickup 60 min · illustrative. Compare the fixed-step run with an event-driven thermal solution. Relay protection is bypassed for this test.
No measurement yet.
∑ The scienceEquations, assumptions and numerical checks +

Building thermal memory

Each representative home is a one-zone thermal mass. While heating is unavailable, indoor temperature relaxes toward outdoor temperature. When the heat pump runs, useful heat is added:

dT/dt = (Tout − T)/τ + COP · Pheat · u / C

Here τ = C/UA, where C is effective heat capacity, UA is the heat-loss coefficient, and u is the thermostat state (zero or one). The exact first-order solution is used at every fixed simulation step.

The thermostat switches on below Tset − ΔT/2 and off above Tset + ΔT/2. A wider deadband spreads switching events over time.

From homes to feeder loading

P = N · mean(Pbase + u Pheat)
S = P / pf    I = P / (√3 VLL pf)

The model uses a balanced three-phase, 11 kV feeder and a fixed illustrative power factor of 0.95. Transformer loading is S divided by the selected kVA rating.

Transformer thermal proxy

dθ/dt = (55 · L1.6 − θ) / τtr

θ is a single thermal-rise state, L is per-unit apparent loading, and τtr is the illustrative thermal time constant. The displayed top-oil proxy is outdoor temperature plus θ. This is a teaching model, not an insulation-life or loading-guide calculation.

Protection trip

An illustrative definite-time relay opens the feeder if loading remains above 1.35 pu for 8 minutes. Those settings are deliberately simplified and are not protection recommendations. Once open, the model removes the electrical load and lets the thermal proxy cool.

MODEL VALIDATION

Independent numerical checks

RUNNING
What is simplified?

The 48 building groups represent a scaled population; their thermal properties and base loads are illustrative. The feeder is balanced and has no explicit cable impedance, voltage drop, phase imbalance, voltage-dependent load, occupancy schedule, hot-water demand, or detailed heat-pump defrost cycle. The transformer is represented by one thermal state. The relay is a simple teaching threshold. The model demonstrates a mechanism, not a prediction for a real utility feeder.

Values labelled textbook refer to standard physical relationships. Values labelled illustrative are chosen for this model; values labelled scaled represent the model population rather than a measured street.

Made with 🤖 ChatGPT