Transmission Line Loss: Sent vs Delivered Power along the Line (2D)

A line from power station to town: the same power at different voltages, lengths and conductor sizes, with the heat lost in the wires over a daily load cycle.

Switch to 3D
Controls

Presets

Parameters

Model checks

The science

Why high voltage. A line must deliver power P. At voltage V the current is I = P/(√3 V cosφ) (three-phase AC) or I = P/(2V) (bipolar DC), and the conductors turn I2R into heat: Ploss = 3 I2R (AC) or 2 I2R (DC). With R = ρL/A the loss share scales as P L /(V2 A cos2φ): doubling the voltage cuts it to a quarter, doubling the line doubles it.

Model. Aluminium, ρ = 0.0282 Ω mm²/m, series reactance 0.35 Ω/km for AC. The receiving end is held at nominal voltage and the sending end is found from the phasor equation Vs = Vr + I (R + jX); the load follows f(h) = 1 + a sin(2π(h−9)/24), so loss follows f² and the daily loss energy is Ploss,0·24·(1 + a²/2): heavier peaks cost more than the average suggests.

Simplifications. Short-line (series) model: no shunt line charging, corona, skin effect, temperature dependence of resistance, or transformer and converter-station losses (HVDC terminals cost roughly 1 to 2 % each in real schemes, which is why HVDC wins only on long lines). Ratings, sag and clearances are not modelled. Checks: sending-end minus receiving-end power against I²R; scaling laws; trapezoid integral against the closed form; voltage drop against its second-order bound.

-
-