The science
What this lab shows. A refrigerator moves heat out of a cold cabinet into a warmer room by circulating a refrigerant through four steps: evaporation (absorbs heat, 4 to 1), compression (1 to 2, costs work), condensation (rejects heat, 2 to 3) and expansion through a valve (3 to 4, cools the fluid). The cabinet warms through its walls and cools while the compressor runs; a thermostat switches it on and off.
1. First law for each component (per kg of refrigerant):
qe = h1 - h4, w = h2 - h1, qc = h2 - h3 = qe + w, h4 = h3 (throttling)
COP = qe / w ≤ COPCarnot = Te / (Tc - Te)
The real COP is well below the Carnot value because of the throttling loss, superheat, compressor losses and non-zero temperature approaches. A hotter room (higher Tc) or a colder cabinet (lower Te) lowers both.
2. Refrigerant model. A teaching model in the style of R134a: the saturation pressure follows Clausius-Clapeyron, ln p = A - B/T (A = 15.52, B = 2691 K, p in kPa), within about 1 % of the table between 0 and 40 C; the latent heat is hfg = 198.6 - 0.89 T (kJ/kg, T in C), the liquid heat capacity is 1.40 kJ/(kg K), and the vapour is an ideal gas with γ = 1.12 and R = 0.0815 kJ/(kg K). The compressor outlet follows isentropic compression T2s = T1 (pc/pe)(γ-1)/γ and h2 = h1 + (h2s - h1)/ηis. After the valve the fluid is a liquid-vapour mixture with quality x4 = (h4 - hf)/hfg.
3. Compressor flow. The mass flow is m-dot = ηv Vsw N ρ1, with volumetric efficiency ηv = 1 - c [ (pc/pe)1/γ - 1 ] for clearance fraction c: a higher pressure ratio re-expands more trapped gas and pumps less.
4. Cabinet. C dT/dt = UA (Troom - T) + Qload - Qe while the compressor runs. The evaporating and condensing temperatures follow the cabinet and room temperatures through fixed approaches, so the cycle moves as the cabinet cools.
Checks (run in the page). (1) and (2) the saturation fit against R134a table values at 0 C (293 kPa) and 40 C (1017 kPa); (3) the first law qc = qe + w; (4) the second law: the real COP is below the Carnot COP and compressor entropy generation is non-negative; (5) at ηis = 1 the outlet temperature equals the isentropic relation; (6) over a three-hour run the cabinet energy change equals the integral of leak minus cooling.
Simplifications. The refrigerant is not exactly R134a: the property correlations are simple fits; there is no pressure drop in pipes and heat exchangers, no oil, no frost, and the temperature approaches are constants (real heat exchangers have them depend on load and fan speed). The vapour is treated as an ideal gas. Heat leak and food load are lumped. Use it to understand trends, not to size a machine.