Why the coil frosts. In heating mode the outdoor coil runs colder than the air. When its surface is below 0 °C and the air carries more water vapour than saturated air at the coil temperature, vapour deposits as frost at a rate r0 = kair (ωair - ωice(Tcoil)). Humidity ratios come from the Magnus saturation pressures (over water for the air, over ice for the coil). The worst frosting is near 0 to 5 °C with high humidity: warm enough to be wet, cold enough for the coil to be below freezing.
Capacity decay. Frost blocks the air path, so airflow and heat pick-up fall as the layer grows: dm/dt = r0(1 - m/mc), which gives m = mc(1 - e-t/τ), τ = mc/r0, and a capacity Q = Q0 e-t/τ at constant compressor power. A reverse-cycle defrost of duration td melts the frost using heat drawn from the building: E = mf(Lf + cice|Tc|)/ηd, with ηd = 0.4 of that heat actually melting frost.
Optimum interval. The cycle COP is [Q0τ(1 - e-T/τ) - E(T)] / [P0(T + td)]. Defrosting too often wastes heat on defrosts, too rarely runs on a blocked coil; the best interval satisfies H'(T)(T + td) = H(T): the marginal net heating rate equals the average.
Checks. Golden-section optimum against bisection on the stationarity condition; RK4 frost growth against the closed form; saturation pressures against published tables; and the second-law bound on the clean-coil COP.
Simplifications. Constant compressor power and constant air mass flow when clean, a lumped coil, linear airflow blockage, a fixed defrost efficiency, no frost density change, no fan or indoor-side dynamics, and a single capacity-versus-temperature slope. Numbers are representative, not those of a product.