Presets
Playback
Apparatus
Model checks
The science
What is modelled
Every home draws an everyday base load with an evening peak. If each car starts charging the moment it arrives, the charging adds to that peak. Smart charging delivers the same total energy but places it where the base load is lowest, which is called valley filling.
Equations
- Arrival times are the normal quantiles
ti = μ + σ Φ−1((i + 0.5)/N); each car charges at power P forD = E / Phours. - Expected cars charging at time t:
N [Φ((t − μ)/σ) − Φ((t − D − μ)/σ)]. - Smart schedule: water-filling, charging power in each window bin
min(N P, max(0, λ − base))with the level λ found by bisection so that the energy equals N E.
Checks run in the page
- Energy conservation: both schedules deliver the same kilowatt-hours.
- Valley filling: equal level in filled periods and the flat lower bound.
- Plug-in peak against the normal-arrival expectation.
Honest simplifications
Every car needs the same energy, charging power is constant and lossless, the base load is a smooth made-up profile, the transformer limit is a plain kVA line (no thermal ageing model), and smart charging is assumed to have perfect knowledge of the base load.
What to try
- Press Fast chargers, overload and see the plug-in peak cross the transformer rating while the smart peak does not.
- Press Short window (tight) and watch the smart schedule run out of room.
- Press Spread arrivals: wide arrival times already flatten the plug-in peak.