Power Transformer Flux — 2D

Drive a transformer and watch core flux, B-H trajectory, magnetising current and inrush.

Switch to 3D

Presets

Playback

Parameters

Layers

Model checks

The science

Faraday's law ties the core flux to the applied voltage: v1 = R1 i1 + N1 A dB/dt, so for a sine drive the peak flux density is Bpk = V√2 / (ω N1 A). The secondary sees v2 = N2 A dB/dt − R2 i2.

Ampere's law gives the magnetising current: N1 i1 − N2 i2 = H l. The core material is modelled as B = Bs tanh(H/Hc) + μ0 H; near Bs the permeability collapses and a small voltage excess (or residual flux at switch-on) draws a large current spike.

Simplifications: anhysteretic core (no hysteresis or eddy-current loss, so efficiency shows copper loss only), no leakage inductance, no winding capacitance, resistive load only. Core geometry is fixed: A = 100 cm², magnetic path 0.5 m, N1 = 200.

What to try
  • Preset Inrush: with 1.2 T residual flux the first half-cycle drives the core past saturation and the current spikes.
  • Raise the voltage or lower the frequency: Bpk grows as V/f and the current waveform turns spiky.
  • Load the secondary: i1 follows i2 times the turns ratio while the core flux hardly changes.
Primary and secondary voltage
Primary and secondary current
B-H trajectory over the saturation curve
Core flux density B(t)