Presets
Playback
Apparatus
Power
Model checks
The science
What is modelled
A cold store loses cold in three ways: heat conducts in through the walls, warm air comes in when the doors open, and lights and equipment add heat inside. A refrigeration plant pumps that heat out, and the work it needs depends on the temperature difference it works across, so a warm climate costs much more electricity. If the power fails, only the leak through the walls warms the contents, and the large thermal mass makes this very slow.
Equations
- Wall
U = 1 / (d/kins + dc/kc + 2 Rfilm), leakQ = U A (Tout − Tin). - Door infiltration
ρ cp Vdoor ΔTper opening. - Plant
COP = η Tc / (Th − Tc)andW = Q / COP. - Power cut
C dT/dt = U A (Tout − T), soT(t) = Tout − (Tout − T0) e−t/τwithτ = C / UA.
Checks run in the page
- A finite-volume solution of conduction through the layered wall against the sum of resistances.
- The second law for the refrigeration plant, with zero entropy generation for the ideal one.
- A Runge-Kutta power-cut warm-up against the exact exponential.
- The convergence of the hourly yearly electricity sum.
Honest simplifications
The vault is a lumped cube-like volume of one temperature, the contents are a single thermal mass, humidity, frost on the evaporator, ground temperature layers and defrost cycles are left out, the plant efficiency is a fixed fraction of the Carnot limit and the outside swing is a plain sine wave. A real vault needs a proper design with measured data.
What to try
- Tick Cut the power and watch the vault warm slowly, then see the days to the limit in the readout.
- Press Thin insulation to see the leak and the yearly electricity grow, and the safety time shrink.
- Press Warm climate to see how the plant COP falls and the electricity bill climbs.