Every watt drawn by the servers leaves as heat in the air, so the air flow follows from the heat balance and the temperature rise across the servers. If some of the hot exhaust air leaks back to the inlets, the servers breathe warmer air. The fans take more power as the cube of the flow, the chiller takes the heat load divided by its coefficient of performance, and the PUE is the total site power divided by the IT power. When cooling is lost the room heats at a rate set by its thermal mass.
Equations
- Airflow
V = P / (ρ cp ΔT). - Inlet temperature with recirculation
Tin = Ts + r ΔT / (1 − r). - Fan power
Pf = V Δp / η, withΔp ∝ V2, soPf ∝ V3. - Chiller
W = Q / COP,PUE = (P + Pf + W + losses) / P. - Ride-through
t = C (Tmax − Tin) / Q.
Checks run in the page
- The airflow against the data-centre rule of thumb in cfm.
- The controlled room temperature settling to the cold-aisle value, with the energy balance.
- The time to reach 32 degrees after a failure, stepped against the closed form.
- The fan affinity exponents from a fan curve meeting a duct curve.
Honest simplifications
The air is treated as one well-mixed cold aisle and one hot aisle, the fan and duct curves are single parabolas, the chiller efficiency rises 3 % per kelvin of supply temperature, the room is one lumped thermal mass and the servers are not throttled when they get hot. Use it for the trends, not for designing a facility.
What to try
- Press Leaky containment and watch the server inlet pass 27 C.
- Press Warm supply air to see the PUE fall as the chiller works less.
- Press Chiller trips, run at 8x speed and see the room reach the limit.