Equations used
Q = q × A · total floor load
Rᵢ = q × Aᵢ · reaction at each tributary support zone
σ = Rmax / (πd²/4) · reference compression stress
δ = Rmax × L / (A × E) · idealised elastic shortening
Qmodel = ΣRᵢ · independent load-balance check
Model constants
Stage area: 200 m² · supports: 18 · reference post diameter: 0.637 m (derived from the largest pillar’s reported 2 m girth) · reference length: 12 m · zelkova modulus: 8.8 GPa as adopted in the 2008 study. The default 2.0 kN/m² load is an illustrative scenario, not a historic design value or visitor limit.
What is simplified
The 18 posts use a regular three-by-six grid with tributary areas summing to 200 m². The calculator is a static vertical-load teaching model, not a capacity rating. It excludes bending, shear, joint slip, timber moisture, decay, foundation movement and earthquake dynamics.
Evidence labels
Documented: 1633 reconstruction, approximate 200 m² stage, 18 zelkova pillars, largest-pillar dimensions, hinoki floor boards, through-beam joints and hipped hinoki-bark roof.
Scholarly model: 8.8 GPa zelkova modulus adopted by the 2008 earthquake-response study.
Interpretive: regular post grid, exact member profiles, joint geometry, terrain, roof curvature and vegetation.
Sources
Educational reconstruction; details marked as reconstruction are interpretive.